DATE : June 4, 1997
TO: Linda James, Director, Planning and Zoning Department
FROM: Joseph Silva, Fire Marshal
SUBJECT: Tractor- & Trailer- Repair- Shop 1311 Andy Lane
If the above referenced project is approved the following
requirements will need to be met for Fire Protection:
1 . Premises Identification. All numbers or addresses shall be 6"
high and placed on the front of the building, above the Office
door, and be clearly visible from the street. The numbers shall
contrast with their background. UFC 901 .4 .4
2 . Portable Fire Extinguishers shall be installed in occupancies
and locations as set forth in this code and as required by the
Chief. UFC 1002. 1 Fire Extinguishers shall have a minimum rating
of the 4A 60BC size and have the top of the extinguisher hung 3' to
5' off the floor. One fire extinguisher shall be located in such a
at the office door.
3 . Repairs will have to be limited exchange of parts and
maintenance not requiring open flame or welding. The building
under this use is considered a S-3 use in the 1994 Unifotitr Building
Code Table 3-A.