HomeMy WebLinkAbout03 Public Agency PUBLIC AGENCY
ITEM DATE SUBMITTED BY
PA- I - fireA)efar+ SuvuD , 199P4- t S'1\V0.
?A- 2 - ekol:o.ae,t, I /
PA -3 -6Luiv ID, l Goan, Cali _
PR - 2 Cr �u 9 , Ig6i TroLA
CALDWELL FIRE DEPARTMENT
• .� ' CITY OF CALDWELL
'"k I� - ��i 310 South 7th Avenue
lti CALDWELL,IDAHO 83605 Protecting Your Property Saving Lives
w fyg0 o (208)455-3032
DATE: June 10, 1997
TO: Caldwell Development Services
FROM: Joseph Silva, Fire Marshal
SUBJECT: Riverstone Restaurant
If the project is approved the following would be the requirements
for minimum fire protection:
1 . That a fire-flow of 1, 500 gallons per minute plus the amount
needed for the activation of the sprinkler system be available to
service the entire project. One fire hydrant shall be placed on
the West end of the landscape island. 1994 UFC Appendix III-A
2 . An automatic sprinkler system shall be installed in rooms used
by the occupants for the consumption of alcoholic beverages and
unseparated room and assembly uses exceeds 5, 000 square feet. That
the building be sprinkled per NFPA 13 . Rooms 1994 Uniform Fire
Code 1003 .2 .3 . 1
3. That the building be provided with a Fire Alarm System which
meets the requirements of NFPA 72 . 1994 Uniform Fire Code
1007.2. 9. 1 . 1
4 . That the building sprinkler system shall be monitored if the
number of heads exceeds 100 per the 1994 Uniform Fire Code 1003.3. 1
5. That a fire department hookup for the sprinkler system be
provided 40' from the building at the Southeast corner of the
structure.
6. That all driveways be 26-' wide around the building with 28'
inside radius and 48' outside radius. Access Std. 3/92
II ' ✓f1
osep Silva
sire Marshal
fjQILVL
JUN Ile 11
ii
,.,✓
_____ ■
PA - I
M E M O
6-13-97
TO: PLANNING AND ZONING
FROM: ENGINEERING
SUBJECT: A REQUEST FOR A SPECIAL USE PERMIT TO CONSTRUCT
AND OPERATE A RESTAURANT. BREWERY AND BAKERY AT CHICAGO AVE. AND
THE BOISE RIVER.
COMMENTS
1 STAMPED ENGINEERED CALCULATIONS AND DESIGN FOR A STORM WATER
RETENTION FACILITY MUST BE SUBMITTED AND APPROVED.
2 . CURB. GUTTER. SIDEWALK AND PAVEMENT MUST BE EXTENDED ALONG
THE PROPERTY LINE ON CHICAGO STREET.
3 . WASTE STRENGTHS AND FLOWS MUST BE CALCULATED FOR SEWER FEES.
4 . PARKING LOT DIMENSIONS NEED TO BE 19 FEET LONG INSTEAD OF 18
FEET LONG .
5 . APPROVAL OF RIVERSIDE IRRIGATION DISTRICT FOR PROJECT.
6 . CONSTRUCTION PLANS AND PROFILES OF SEWER AND WATER MUST BE
SUBMITTED TO ENGINEERING AND D.E.Q. FOR APPROVAL.
7. WATER AND SEWER ARE LOCATED AT CHICAGO AND BELMONT STREETS.
8 . THE ENTRANCE TO THE PROPERTY AS SHOWN IS NOT A PART OF THE
PROPERTY. THIS ENTRANCE NEEDS TO BE COVERED EITHER AS A DEED
TO THE PROPERTY OR AS A PERMANENT INGRESS AND EGRESS
EASEMENT. IF AN EASEMENT IS NOT OBTAINABLE. THE ENTRANCE TO
THE PROPERTY MUST BE LIMITED TO THE ACTUAL PROPERTY FRONTAGE
ON CHICAGO STREET.
?A -a
I State of Idaho —
D DEPARTMENT OF WATER RESOURCES
R
W Western Region, 2735 Airport Way, Boise, Idaho 83705-5082 - (208) 334-2190
YY
R FAX (208) 334-2348
PHILIP E.BATT
GOVERNOR
KARL J.DREHER
DIRECTOR
June 10, 1997
Linda James
City of Caldwell
621 Cleveland Blvd.
Caldwell ID 0.;000
RE: Case #SUP-14-97 & VAR-03-97
Dear Ms James,
This office has received a request for comments on the above
referenced proposal. We would like to offer the following
information:
The Idaho Department of Water Resources administers the Stream
Protection Act. The Act requires that before any activity can take
place below the ordinary high water mark of a perennial stream, a
Stream Channel Alteration permit must be obtained from this
Department.
The applicant should be aware that applications are required to be
submitted sixty (60) days before the work is scheduled to take
place. The Department is available to review preliminary plans and
offer comments.
Thank you for 4-hi c opportunity to rcmmo„t Dl n=.-n r,nntac this
office if you have any questions about the Stream Protection
Program, or the permitting process.
Sincerely
- 44L-4-- E-kr---
M. ene Gibson
Stream Protection Specialist
MGG:kg
Mt 1i u
— Celebrating Our Centennial Year of Service to Idaho 1895-1995 ---
j
DONALD R. LENZ OPERATING AGENCY FOR 167,000
CHAIRMAN OF THE BOARD BCE PROJECT BOARD OF CONTIissL ACRES FOR THE FOLLOWING
HENRY WEICK IRRIGATION DISTRICTS
(FORMERLY BOISE U.S.RECLAMATION PROJECT)
VICE CHAIRMAN OF THE BOARD
KENNETH HENLEY 2465 OVERLAND ROAD NAMPA-MERIDIAN DISTRICT
PROJECT MANAGER BOISE,IDAHO 83705-3173 BOISE-KUNA DISTRICT
PAUL J.DEVEAU WILDER DISTRICT
ASSISTANT PROJECT MANAGER NEW YORK DISTRICT
BEND DISTRICT
JUDITH A.JEMMETT
SECRETARY-TREASURER
ELVA FISCHER TEL:(208)344-1141
ASSISTANT SECRETARY-TREASURER FAX:(208)344-1437
June 9, 1997
Linda James, Community Development Director
City of Caldwell
Community Development Dept.
621 Cleveland Blvd.
Caldwell, ID. 83605
RE: Janie M. Hendrix/ SUP-14-97, & VAR-03-97
Dear Ms. James:
After reviewing the information supplied by your office, it appears the applications for the above
mentioned property are out of our jurisdiction.
If you have any further questions or comments regarding this matter, please do not hesitate to
contact me at (208) 344-1141.
Sincerely,
-011 / 1/L-t----7'
Troy Upshaw
Urbanization Coordinator
tlu/tu
cc: file: HendrixSUP1497
D a 1
JUN 1 v