DATE: April 3, 2000
TO: Linda James, Community Development Director
FROM: Douglas Brown,Fire Marshal
SUBJECT: CASE NO. SUP-80-00/Child Care Center
APPLICANT: Naomi Kay Rush
It is understood that this proposed project is being reviewed for a Special Use Permit in order to
occupy a former educational building, located at 4515 E. Ustick Road, and operate it as a Day Care
Center.
I have already been contacted by the applicant and performed a preliminary State Fire Marshal's
Inspection for Day Care Center at the proposed site. Attached is a copy of my correspondence of
conditions required by the CFD in order to open and operate such a facility at that location.
This proposed project is supported by the Fire Marshal as a potentially good use of a currently
empty building.
If there are concerns or questions regarding any of these conditions please contact us for
explanation or assistance.
001,14, Ree-v1,-...„-
Douglas Brown
Fire Marshal
Attachment: CFD memo of March 27, 2000 to Ms. Naomi Kay Rush
P4— (
rlise,
� x CALDWEL L FIRE DEPARTMENT
..
" r CITY OF CALDWELL
310 South 7th Avenue
1k CALDWELL, IDAHO 83605 Protecting
Your Property
Saving Lives� , (208) 455-3032 46r7 o O t
DATE: March 27, 2000
TO: Ms . Naomi Kay Rush
FROM: Douglas Brown, Fire Marshal
SUBJECT: Kid' s Club Day Care Center Proposal
4515 E. Ustick
It was good to meet you this morning at the site of your proposed
day care center.
The following are the requirements to provide minimum fire
protection for your project if the number of children using the
facility is 49 or less :
1 . Exit signage is required on all exit doors .
2 . One (1) 2A: 10BC rated fire extinguisher must be provided in a
visible and easy to access location.
3 . The address of the building must be posted facing Ustick Road
in a minimum of eight inch (8" ) high numbers which contrast
with the background.
4 . Battery operated smoke detectors must be provided in all
classrooms and common areas .
5 . All turn-knob deadbolts must be removed from all exit doors .
6 . All exit doors must open outward with a minimal effort to
open. (The stuck doors need to be fixed. )
7 . Fire escape plans, utilizing reasonably "to scale" drawings
of the floor plan of the facility, need to be posted in each
classroom with the exits and exit routes clearly marked.
8 . The void spaces in the exterior walls in the front part of
each classroom must be covered or converted into a different
use so children can' t hide or become stuck in them.
,A) - / (a)
9 . Each classroom must be identified with signage indicating a
letter, number or special name for each room.
10 . All missing electrical outlet cover plates must be replaced.
11 . The Romex electrical wire supplying power to the exterior
light in the classroom facing Ustick Road must be installed
per National Electrical Code standards (placed in conduit) .
12 . Some kind of evacuation signal is required (horn or whistle)
to alert the children of a fire and to evacuate the building
to a pre-arranged and safe location outside .
13 . If fencing is installed around the sides or rear of building
there must be sufficient man-gates to allow access for
emergencies .
If it is your intention to use this facility for 50, up to 102
children, then the following additional conditions apply:
1 . Plans for an approved fire alarm system, per NFPA 72
standards, must be submitted, approved, installed and made
operational prior to occupancy.
2 . All exit doors must be equipped with approved panic hardware.
3 . All exits must have approved illuminated exit signage .
4 . Emergency backup lighting must be provided throughout the
building.
5 . The outside of all exit doors must have illumination.
6 . The occupant load must be prominently posted.
The Caldwell Fire Department acknowledges your request for a
daycare center inspection for your State Fire Marshal approval and
will keep your request on file, pending the outcome of your
special use permit request currently pending before the City of
Caldwell (Case No. SUP-80-00) .
a 0 urivez.44,.. .,
Douglas Brown
Fire Marshal