HomeMy WebLinkAboutCFDMemo_Soterra2403 Blaine Street • Caldwell, ID 83605 • Phone 208-649-1266 • Fax 208-455-3014 Date 3/9/2026 Caldwell City – Planning and Zoning Re: Case Number: SPP26-000001 Soterra No. 2 Dear, Planning & Zoning The Caldwell City Fire Department District has reviewed and can approve the application subject to compliance with all the following code requirements and conditions of approval. Any deviation from this plan is subject to Fire Department approval. Please note that unless stated otherwise, this memo represents the requirements of the 2018 International Fire Code (IFC) as adopted by the Idaho State Fire Marshal’s Office. Caldwell Fire Department Details Station 12 724 E Ustick Rd. Caldwell, National Standards for Travel Time (90% of time) for first arriving unit: 4 minutes Nearest Fire Station: 0.6 Miles Closest fire station (in miles) to site: 1 Min. ☐ If yes, please explain under “Adverse Impact Comments, Recommendations, and Fiscal Impact”. •Ongoing population increases will directly affect service levels until CFD can enhance and expand its operational capabilities. ☐ 0.6 Miles 403 Blaine Street • Caldwell, ID 83605 • Phone 208-649-1266 • Fax 208-455-3014 Distance from Station Service Expectation Staffing & Apparatus Typical Response Time Goal 0–1 mile Immediate—high- priority First-due company (engine) ≤4min travel, ≤5min total 1–2 miles Very rapid—high- priority First-due company, backup ≤4min travel, ≤5min total 2–3 miles Rapid—standard coverage First-due w/ backup ≤6min travel, ≤9min total (full alarm) 3–4 miles Slower—moderate Closest available, limited 6–8min travel 4–5 miles Extended Closest company, delayed >8min travel, variable Properties located 3–4 miles from a fire station are at the limit of effective coverage and may experience service delays. Developments beyond 5 miles are generally not recognized by ISO as having fire protection, and response to these areas will be significantly delayed. Conditions: 1. Fire hydrants, capable of producing the required fire flow, shall be located along approved fire lanes. Fire hydrant spacing shall meet the requirements of IFC table C105.1.1 (IFC 507.3, IFC B105.2, IFC C105). 2. Roadway serving a fire hydrant shall be a minimum of 26-feet in width. (IFC D103.1) 3. Dead-end fire apparatus access roads exceeding 150 feet (45 720 mm) in length shall be provided with an approved area for turning around fire apparatus. (IFC 503.2.5) 4. Fire apparatus access roads shall extend to within 150 feet of all portions of the exterior walls of the first story of a building measured by an approved route around the exterior of the building or facility. (IFC 503.1.1) 5. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet and an unobstructed vertical clearance of not less than 13 feet 6 inches. (IFC 503.2.1) 403 Blaine Street • Caldwell, ID 83605 • Phone 208-649-1266 • Fax 208-455-3014 6. The minimum outside turning radius of a fire apparatus access road shall be 48 feet. The minimum inside turning radius shall be 28 feet. (IFC 503.2.4) 7. Fire apparatus access roads shall have an approved driving surface of asphalt, concrete or other approved driving surface and can support the imposed load of fire apparatus weighing at least 80,000 pounds. Please provide documentation the road surface meets this standard. (IFC D102.1) 8. Fire apparatus access roads shall not exceed 10 percent in grade. (IFC D103.2) 9. For streets having a width less than 33 feet back of curb to back of curb parking shall be restricted on one side; for streets having a width less than 27 feet back of curb to back of curb parking shall be restricted on both sides. A note on the face of the final plat is required noting the parking restriction prior to signing of the final plat. In addition, No Parking signs shall be installed in accordance with the requirements of the IFC. (IFC 503.8) 10. Approved secondary access roads shall be provided per section D106 of the 2018 IFC. 11. An automatic fire sprinkler system installed per NFPA 13 may be required. 12. Fire hydrants serving building FDC’s shall be located not more than 150’away 13. A phasing plan shall be included in documentation to city at time of submittal in accordance with infrastructure 2018 IFC. 14. Where fire apparatus access roads or a water supply for fire protection are required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except where approved alternative methods of protection are provided. Temporary street signs shall be installed at each street intersection where construction of new roadways allows passage by vehicles in accordance with (IFC Section 505.2. 15. SECTION D107 ONE- OR TWO-FAMILY RESIDENTIAL DEVELOPMENTS D107.1 One- or two-family dwelling residential developments. Developments of 403 Blaine Street • Caldwell, ID 83605 • Phone 208-649-1266 • Fax 208-455-3014 one- or two-family dwellings where the number of dwelling units exceeds 30 shall be provided with two separate and approved fire apparatus access roads. Exceptions: 1. Where there are more than 30 dwelling units on a single public or private fire apparatus access road and all dwelling units are equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3, access from two directions shall not be required. 16. SECTION D104 COMMERCIAL AND INDUSTRIAL DEVELOPMENTS D104.1 Buildings exceeding three stories or 30 feet in height. Buildings or facilities exceeding 30 feet (9144 mm) or three stories in height shall have not fewer than two means of fire apparatus access for each structure. 17. D104.2 Buildings exceeding 62,000 square feet in area. Buildings or facilities having a gross building area of more than 62,000 square feet (5760 m2) shall be provided with two separate and approved fire apparatus access roads. a. Exception: Projects having a gross building area of up to 124,000 square feet (11 520 m2 ) that have a single approved fire apparatus access road where all buildings are equipped throughout with approved automatic sprinkler systems. 18. D104.3 Remoteness. Where two fire apparatus access roads are required, they shall be placed a distance apart equal to not less than one half of the length of the maximum overall diagonal dimension of the lot or area to be served, measured in a straight line between accesses. 19. D105.1 Where required. Where the vertical distance between the grade plane and the highest roof surface exceeds 30 feet (9144 mm), approved aerial fire apparatus access roads shall be provided. For purposes of this section, the highest roof surface shall be determined by measurement to the eave of a pitched roof, the intersection of the roof to the exterior wall, or the top of parapet walls, whichever is greater. 403 Blaine Street • Caldwell, ID 83605 • Phone 208-649-1266 • Fax 208-455-3014 20. D105.2 Width. Aerial fire apparatus access roads shall have a minimum unobstructed width of 26 ft. (7925 mm), exclusive of shoulders, in the immediate vicinity of the building or portion thereof. 21. D105.3 Proximity to building. One or more of the required access routes meeting this condition shall be located not less than 15 feet (4572 mm) and not greater than 30 feet (9144 mm) from the building, and shall be positioned parallel to one entire side of the building. The side of the building on which the aerial fire apparatus access road is positioned shall be approved by the fire code official. 22. D105.4 Obstructions. Overhead utility and power lines shall not be located over the aerial fire apparatus access road or between the aerial fire apparatus road and the building. Other obstructions shall be permitted to be placed with the approval of the fire code official. 23. An Automatic Fire Detection System and Fire Alarm System may be required based on the occupancy type and evaluation of hazards with the structure. 901.4.4 24. An eKnox lock box, shall be installed on the outside of the building by the main entrance and by the sprinkler room. Additional eKnox Key boxes may be required based on occupancy and proximity of other Boxes. Each eKnox Box shall have labeled master keys to every lock within the structure. The final number and location shall be with the approval of the Caldwell Fire Marshal or designee. 506.1 25. Emergency Responder Radio Coverage: New buildings shall have approved radio coverage for emergency responders within the building based on the existing coverage levels of the public safety communication systems utilized by the jurisdiction, measured at the exterior of the building. This section shall not require improvement of the existing public safety communication systems. 510. General Requirement: Fire Department required fire hydrants, access, and street identification shall be installed prior to construction or storage of combustible materials on site. Provisions may be made for temporary access and identification measures. 403 Blaine Street • Caldwell, ID 83605 • Phone 208-649-1266 • Fax 208-455-3014 Specific building construction requirements of the International Building Code, International Fire Code and City of Caldwell Code will apply. However, these provisions are best addressed by a licensed Architect at time of building permit application. Regards, Alan Perry Deputy Chief Fire Marshal Caldwell Rural Fire Protection District Aperry@cityofcaldwell.org