HomeMy WebLinkAboutCFD_Homesteads at Wilson Creek_V2 403 Blaine Street  Caldwell, ID 83605  Phone 208-649-1266  Fax 208-455-3014 Date 7/9/2024 Caldwell City – Planning and Zoning Re: Case Number PUD24-000003 Homesteads at Wilson Creek Dear Angelica Gomez, Planning & Zoning The Caldwell City Fire Department District has reviewed and can approve the application subject to compliance with all the following code requirements and conditions of approval. Any deviation from this plan is subject to Fire Department approval. Please note that unless stated otherwise, this memo represents the requirements of the 2018 International Fire Code (IFC) as adopted by the Idaho State Fire Marshal’s Office. Conditions: 1. Fire hydrants, capable of producing the required fire flow, shall be located along approved fire lanes. Fire hydrant spacing shall meet the requirements of IFC table C105.1.1 (IFC 507.3, IFC B105.2, IFC C105). 2. Roadway serving a fire hydrant shall be a minimum of 26-feet in width. (IFC D103.1) 3. Dead-end fire apparatus access roads exceeding 150 feet (45 720 mm) in length shall be provided with an approved area for turning around fire apparatus. (IFC 503.2.5) 4. Fire apparatus access roads shall extend to within 150 feet of all portions of the exterior walls of the first story of a building measured by an approved route around the exterior of the building or facility. (IFC 503.1.1) 5. Fire apparatus access roads shall have an unobstructed width of not less than 20 feet and an unobstructed vertical clearance of not less than 13 feet 6 inches. (IFC 503.2.1) 6. The minimum outside turning radius of a fire apparatus access road shall be 48 feet. The minimum inside turning radius shall be 28 feet. (IFC 503.2.4) 7. Fire apparatus access roads shall have an approved driving surface of asphalt, concrete or other approved driving surface and can support the imposed load of fire apparatus weighing at least 80,000 pounds. Please 403 Blaine Street  Caldwell, ID 83605  Phone 208-649-1266  Fax 208-455-3014 provide documentation the road surface meets this standard. (IFC D102.1) 8. Fire apparatus access roads shall not exceed 10 percent in grade. (IFC D103.2) 9. Access gates shall comply with requirements of the IFC. If gates are electronically operated, they shall be equipped with an automatic opening mechanism activated by the eknox system. Manual gates shall be secured with a Knox brand padlock (IFC 503.6, D103.5). 10. Approved secondary access roads shall be provided per section D106 of the 2018 IFC. 11. Fire hydrants serving building FDC’s shall be located not more than 150’away 12. Where fire apparatus access roads or a water supply for fire protection are required to be installed, such protection shall be installed and made serviceable prior to and during the time of construction except where approved alternative methods of protection are provided. Temporary street signs shall be installed at each street intersection where construction of new roadways allows passage by vehicles in accordance with (IFC Section 505.2. 13. SECTION D107 ONE- OR TWO-FAMILY RESIDENTIAL DEVELOPMENTS D107.1 One- or two-family dwelling residential developments. Developments of one- or two-family dwellings where the number of dwelling units exceeds 30 shall be provided with two separate and approved fire apparatus access roads. Exceptions: 1. Where there are more than 30 dwelling units on a single public or private fire apparatus access road and all dwelling units are equipped throughout with an approved automatic sprinkler system in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3, access from two directions shall not be required. 403 Blaine Street  Caldwell, ID 83605  Phone 208-649-1266  Fax 208-455-3014 General Requirement: Fire Department required fire hydrants, access, and street identification shall be installed prior to construction or storage of combustible materials on site. Provisions may be made for temporary access and identification measures. Specific building construction requirements of the International Building Code, International Fire Code and City of Caldwell Code will apply. However, these provisions are best addressed by a licensed Architect at time of building permit application. Regards, Alan Perry Deputy Chief Fire Marshal Caldwell Rural Fire Protection District Aperry@cityofcaldwell.org