403 Blaine Street Caldwell, ID 83605 Phone 208-649-1266 Fax 208-455-3014
Date 8/7/2023
Canyon County – Planning and Zoning
Re: SUB22-000028, Baja Spring Subdivision
Dear Robin Collins,
The Caldwell Rural Fire Protection District has reviewed and can approve the
application subject to compliance with all the following code requirements and
conditions of approval. Any deviation from this plan is subject to Fire
Department approval. Please note that unless stated otherwise, this memo
represents the requirements of the 2018 International Fire Code (IFC) as adopted
by the Idaho State Fire Marshal’s Office.
Comments:
1. Fire hydrants, capable of producing the required fire flow, shall be
located along approved fire lanes. Fire hydrant spacing shall meet the
requirements of IFC table C105.1.1 (IFC 507.3, IFC B105.2, IFC C105).
2. Structures greater than 30-feet in height will require aerial fire access
roadways. These roadways shall be a minimum of 26-feet in width and
located at least 15-feet but no more than 30-feet from the building. (IFC
D105)
3. Roadway serving a fire hydrant shall be a minimum of 26-feet in width.
(IFC D103.1)
4. Dead-end fire apparatus access roads exceeding 150 feet (45 720 mm) in
length shall be provided with an approved area for turning around fire
apparatus. (IFC 503.2.5)
5. Fire apparatus access roads shall extend to within 150 feet of all portions
of the exterior walls of the first story of a building measured by an
approved route around the exterior of the building or facility. (IFC 503.1.1)
6. Monument signage for addressing will be required at the entrance and at
all intersections within the project. (IFC 505.1)
7. Fire apparatus access roads shall have an unobstructed width of not less
than 20 feet and an unobstructed vertical clearance of not less than 13
feet 6 inches. (IFC 503.2.1)
8. The minimum outside turning radius of a fire apparatus access road shall
be 48 feet. The minimum inside turning radius shall be 28 feet. (IFC 503.2.4)
9. Fire apparatus access roads shall have an approved driving surface of
asphalt, concrete or other approved driving surface and can support the
imposed load of fire apparatus weighing at least 75,000 pounds. Please
403 Blaine Street Caldwell, ID 83605 Phone 208-649-1266 Fax 208-455-3014
provide documentation the road surface meets this standard. (IFC
D102.1)
10. Fire apparatus access roads shall not exceed 10 percent in grade. (IFC
D103.2)
11. Access gates shall comply with requirements of the IFC. If gates are
electronically operated, they shall be equipped with an automatic
opening mechanism activated by the Opticom system. Manual gates
shall be secured with a Knox brand padlock (IFC 503.6, D103.5).
12. Fire hydrants serving building FDC’s shall be located not more than
150’away.
13. Where fire apparatus access roads or a water supply for fire protection
are required to be installed, such protection shall be installed and made
serviceable prior to and during the time of construction except where
approved alternative methods of protection are provided. Temporary
street signs shall be installed at each street intersection where construction
of new roadways allows passage by vehicles in accordance with (IFC
Section 505.2.)
General Requirement:
Fire Department required fire hydrants, access, and street identification shall be
installed prior to construction or storage of combustible materials on site.
Provisions may be made for temporary access and identification measures.
Specific building construction requirements of the International Building Code,
International Fire Code and City of Caldwell Code will apply. However, these
provisions are best addressed by a licensed Architect at time of building permit
application.
Regards,
Alan Perry
Division Chief
Fire Marshal
Caldwell Rural Fire Protection District